SICK / MODEL

RLY3-TIME100

RLY3 ReLy Safety Relays

SICK RLY3-TIME100 — Application: Stop category 1 evaluation unit; SICK Part Number: 1100688; Safety Contact Configuration: 2 instantaneous N/O + 1 release-delayed N/O.

Application
Stop category 1 evaluation unit
SICK Part Number
1100688
Safety Contact Configuration
2 instantaneous N/O + 1 release-delayed N/O
Power Supply Type
PELV or SELV

Overview

Two instantaneous safety contacts plus one release-delayed contact. The release-delay setting range is not specified in the supplied overview; 12 ms is the listed response time, not the delay setting. Test pulse output count conflicts between p.8 (3) and p.11 (1) and is not published as verified. Application diagnostic outputs conflict: p.8 shows a dash while p.11 shows 2. Diagnostic output specifications are withheld pending the model-specific operating instructions. Use the exact ordering code and the applicable operating instructions. Catalogue ratings describe the module, not the validated safety level of a complete machine. Current availability has not been checked.

Specifications

ApplicationStop category 1 evaluation unit
SICK Part Number1100688
Safety Contact Configuration2 instantaneous N/O + 1 release-delayed N/OImmediate and release-delayed safety paths are distinguished; non-safe feedback, signaling and diagnostic outputs are not included here.
Power Supply TypePELV or SELV
Compatible Sensor TypesSafety sensors with OSSDs; safety sensors with potential-free outputs
Instantaneous Safety Paths (N/O)2
Release-delayed Safety Paths (N/O)1
Nominal Housing Width18 mmNominal housing width. Front-connector envelope and installation dimensions are shown separately in the p.14 drawings.
Connection Typefront connector with spring terminals
Catalogue Safety Integrity LevelSIL3 (IEC 61508) SILCL3 (IEC 62061)Catalogue-stated rating (8021876/2021-10-22). Achievable application safety depends on the circuit, wiring and applicable operating instructions; this is not a certification of the complete machine.
Catalogue Safety CategoryCategory 4 (ISO 13849-1)Catalogue-stated rating (8021876/2021-10-22). Achievable application safety depends on the circuit, wiring and applicable operating instructions; this is not a certification of the complete machine.
Catalogue Performance LevelPL e (ISO 13849-1)Catalogue-stated rating (8021876/2021-10-22). Achievable application safety depends on the circuit, wiring and applicable operating instructions; this is not a certification of the complete machine.
Mission Time20 years (ISO 13849-1)Catalogue-stated rating (8021876/2021-10-22). Achievable application safety depends on the circuit, wiring and applicable operating instructions; this is not a certification of the complete machine.
PFHd (Mean Dangerous Failure Probability per Hour)1.0 x 10^-9 /hCatalogue-stated rating (8021876/2021-10-22). Achievable application safety depends on the circuit, wiring and applicable operating instructions; this is not a certification of the complete machine.
Stop Category (IEC 60204-1)0 for instantaneous paths (13-14, 23-24); 1 for release-delayed path (37-38)TIME1 path-specific stop categories follow footnotes 1 and 2; consult operating instructions for application design.
Listed Monitoring FunctionsDiscrepancy monitoring; Sequence monitoring; Cross-circuit detection; Restart interlock; External device monitoring (EDM)
Resetautomatic manual
Safety Inputs2
Reset Pushbutton / EDM Inputs1
Display ElementsLEDs
Supply Voltage Vs24 V DC (16.8 V to 30 V)
Residual Ripple≤ 2.4 V
Power Consumption≤ 2.5 W (DC)
Safety Input Voltage HIGH24 V DC (11 V to 30 V)
Safety Input Voltage LOW0 V DC (-3 V to 5 V)
Safety Input Current4 mA to 6 mA
Safety Input Test Pulse Width≤ 1 ms
Safety Input Test Pulse Rate≤ 10 Hz
Activation Time Tolerance Between Start Buttons≤ 3 s
Configuration MethodHard wired; DIP switches
Reset / EDM Voltage HIGH24 V DC (11 V to 30 V)
Reset / EDM Voltage LOW0 V DC (-3 V to 5 V)
Reset / EDM Input Current4 mA to 6 mA
Instantaneous Safety Path Response Time12 ms
Instantaneous Safety Contact TypeN/O contacts, positively guided
Safety Contact MaterialSilver alloy, gold flashed
Instantaneous Safety Path Switching Voltage10 V AC to 230 V AC 10 V DC to 230 V DC
Instantaneous Safety Path Switching Current10 mA to 6 A
Maximum Total Safety Path Current12 ATIME1: combined maximum for all 3 safety paths, including the release-delayed path.
Mechanical Life (Switching Cycles)10^7 cycles
Overvoltage CategoryIII (EN 60664-1)
Rated Impulse Withstand Voltage6 kV (EN 60664-1)
Release-delayed Path Response Time12 msThe 12 ms response time is not the selectable release-delay setting. The supplied overview does not specify the release-delay adjustment range.
Release-delayed Safety Contact TypeN/O contacts, positively guidedApplies only to the release-delayed path; do not apply instantaneous contact ratings to this path.
Release-delayed Contact MaterialSilver alloy, gold flashedApplies only to the release-delayed path; do not apply instantaneous contact ratings to this path.
Release-delayed Path Switching Voltage10 V DC to 30 V DCApplies only to the release-delayed path; do not apply instantaneous contact ratings to this path.
Release-delayed Path Switching Current2 mA to 2 AApplies only to the release-delayed path; do not apply instantaneous contact ratings to this path.
Test Pulse Outputs (Not Safe): TypePNP semiconductors, short-circuit protected
Test Pulse Outputs (Not Safe): Output Voltage≥ Vs - 3 V
Test Pulse Outputs (Not Safe): Pulse Width2 ms
Test Pulse Outputs (Not Safe): Pulse Interval40 ms
Weight160 g
Enclosure RatingIP20 (IEC 60529)
Ambient Operating Temperature-25 to +55 °C
Storage Temperature-25 to +70 °C
Air Humidity10 to 95%, non-condensing
Interference EmissionAccording to IEC 61000-6-4Standard identifiers and values are quoted from the 2021 catalogue; no current certificate or complete-system compliance is inferred.
Interference ResistanceAccording to IEC 61326-3-1; IEC 61000-6-2; IEC 60947-5-1Standard identifiers and values are quoted from the 2021 catalogue; no current certificate or complete-system compliance is inferred.

Document

PDFsick-rly3-safety-relays-en.pdfSICK ReLy RLY3 Safety Relays - English Product Information (8021876/2021-10-22) · Shared series document

Request this model

Send the exact ordering code, quantity or product list.

Request a Quote
WhatsApp

Request a Quote

Fields marked * are required.

PDF, XLS, XLSX, CSV, DOC, DOCX, JPG or PNG
Up to 5 files · 10 MB each · 50 MB totalDo not include sensitive personal information or documents you are not permitted to share.

A confirmation page appears only after your inquiry is recorded. For email correspondence, contact sales@brolenz.com.